Fire Sci. Eng. Search

CLOSE


Fire Sci. Eng. > Volume 33(3); 2019 > Article
Fire Science and Engineering 2019;33(3):84-90.
DOI: https://doi.org/10.7731/KIFSE.2019.33.3.084    Published online June 30, 2019.
환경에너지 시설내 화재 및 피난해석
전용한1, 김종윤2
1상지영서대학교 소방안전학과 교수
2서정대학교 소방안전관리과 교수
Fire and Evacuation Analysis in Environmental Energy Facilities
Yong-Han Jeon1, Jong-Yoon Kim2
1Professor, Dept. of Fire Protection and Safety, Sangji-Youngseo College
2Professor, Dept. of Fire Safety Management, Seojeong Univ.
Correspondence:  Jong-Yoon Kim, Tel: +82-31-860-5014, Fax: +82-31-860-5053, 
Email: sweat100@hanmail.net
Received: 23 April 2019   • Revised: 10 May 2019   • Accepted: 13 May 2019
요약
본 연구에서는 환경에너지 시설내 전자기기실 내부의 화재 및 피난을 수치적 해석 방법을 통해 실시하고 평가하였다. 화재 시뮬레이션은 FDS을 이용하여 가시거리, 온도분포, CO의 농도분포 등을 분석하였다. 그 결과를 토대로 피난시뮬레이션인 Pathfinder프로그램을 사용하여, 재실자들의 피난시간을 계산하였으며 피난안전성 평가를 도출하였다. 그 결과 전자기기실 내부의 피난 허용시간은 P-01에서 203.3 s로 가장 단시간 내에 대피가 요구되었으며, P-05에서 398.6 s로 피난 허용시간이 가장 큰 값을 나타내었다. 피난 소요시간 분석 결과 모든 지점에서 모든 재실 인원이 대피가 이루어져 대피자의 안전성이 확보되는 것으로 판단되었다. 특히 이 시뮬레이션의 결과는 피난안전성능을 높이기 위하여 소방설비가 작동하지 않는 경우를 고려한 것으로서 실제 화재 발생 시 소방설비가 작동된다면 보다 우수한 안전을 확보할 수 있을 것으로 사료된다.
Abstract
In this study, a fire and evacuation inside an electronic equipment room in environmental energy facilities were conducted and evaluated using a numerical analysis method. In the fire simulation, the visual distance, temperature distribution, and CO concentration distribution were analyzed using FDS. Based on the results, the Pathfinder program, which is an evacuation simulation, was used to calculate the evacuation time of the occupants and derive an evacuation safety evaluation. As a result, the Available safe Egress time (ASET) of P-01 and P-05 was 203.3 and 398.6 s, respectively. For the Required safety Egress time (RSET) results, all evacuees were evacuated at all points and the safety of the evacuee was secured this simulation showed that the safety evaluation is based on the non - operation of the fire - fighting equipment to improve the safety, making it possible to secure better evacuation safety performance owing to the fire of other fire - fighting facilities.
Key Words: FDS, Pathfinder, Available safe egress time (ASET), Required safety egress time (RSET)


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2024 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next