Fire Science and Engineering 2019;33(6):9-19.
DOI: https://doi.org/10.7731/KIFSE.2019.33.6.009    Published online December 31, 2019.
화원면적 변화에 따른 격자 크기 의존도 및 예측결과 분석
윤홍석1, 황철홍2
1대전대학교 대학원 방재학과 대학원생
2대전대학교 소방방재학과 교수
Analysis of Prediction Results and Grid Size Dependence According to Changes in Fire Area
Hong-Seok Yun1, Cheol-Hong Hwang2
1Graduate Student, Dept. of Disaster Prevention, Daejeon University
2Professor, Department of Fire and Disaster Prevention, Daejeon University
Correspondence:  Cheol-Hong Hwang, Tel: +82-42-280-2592, Fax: +82-42-280-2596, 
Email: chehwang@dju.ac.kr
Received: 18 October 2019   • Revised: 8 November 2019   • Accepted: 19 November 2019
요약
건축물의 화재안전성평가를 위한 화재시뮬레이션에서 화원면적 및 격자크기의 변화는 예측결과에 큰 영향을 미칠 수 있다. 따라서 동일한 최대 열발생률을 갖는 화원의 면적 변화가 구획화재의 예측결과에 미치는 영향이 검토되었으며, 동일한 화원면적의 조건에서 격자크기에 대한 예측결과의 의존도가 동시에 검토되었다. 주요 결과로서, 특성화재직경을 기준으로 6개 이상의 격자가 삽입되면 화원면적이 변화되더라도 격자크기는 화재의 열 및 화학적 특성에 큰 영향을 미치지 않았다. 또한 화원면적의 변화는 구획 내부에서 허용피난시간(ASET)과 관련된 주요 물리량의 예측결과에 상당한 차이를 야기하였다. 그러나 개구부를 기준으로 일정 거리 이상의 구획외부에서는 화원면적의 변화가 전반적 화재특성에 미치는 영향이 크지 않음이 확인되었다.
Abstract
In fire simulations for building fire safety evaluation, changes in the fire area and grid size can significantly influence the prediction results. Therefore, the effects of area changes of the fire source with identical maximum heat release rates on the prediction results of a compartment fire were investigated. The dependence of the prediction results on the grid size using the identical fire area was also examined. No significant changes were observed in the thermal and chemical characteristics of the fires with variable grid sizes, even though the fire area was changed when six or more grids were set based on the fire diameter. In addition, changes in the fire area caused significant differences in the prediction of major physical quantities associated with available safety egress time (ASET) within a compartment. However, the fire area changes did not considerably influence the overall fire characteristics outside the compartment after reaching a certain distance from the opening.
Key Words: Performance-Based Design (PBD), Fire Dynamics Simulator (FDS), Fire Area, Available Safety Egress Time (ASET), Grid Size
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 0 Crossref
  •    
  • 94 View
  • 9 Download
Related articles in Fire Sci. Eng.


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
22, Teheran-ro 7-gil, Gangnam-gu, Seoul 06130, Republic of Korea
Tel: +82-2-555-2450    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2020 by Korean Institute of Fire Science and Engineering. All rights reserved.

Developed in M2community

Close layer
prev next