Fire Sci. Eng. Search

CLOSE


Fire Sci. Eng. > Volume 33(6); 2019 > Article
Fire Science and Engineering 2019;33(6):20-27.
DOI: https://doi.org/10.7731/KIFSE.2019.33.6.020    Published online December 31, 2019.
화재시 열방출 급상승 구간의 수치모형 개발에 관한 연구(로지스틱 함수 및 역함수 곡선)
김종희1, 송준호2, 김건우3, 권오상4, 윤명오5
1서울시립대학교 재난과학과 대학원생
2서울시립대학교 수학과 명예교수
3서울시립대학교 기계정보공학과 대학원생
4한국건설기술연구원 화재안전연구소 수석연구원
5서울시립대학교 재난과학과 교수
Development of a Numerical Model for the Rapidly Increasing Heat Release Rate Period During Fires (Logistic function Curve, Inversed Logistic Function Curve)
Jong-Hee Kim1, Jun-Ho Song2, Gun-Woo Kim3, Oh-Sang Kweon4, Myong-O Yoon5
1Graduate Student, Dept. of Disaster Science, University of Seoul
2Emeritus Professor, Dept. of Mathematics, University of Seoul
3Graduate Student, Dept. of Mechanical and Information Engineering, University of Seoul
4Senior Researcher, Korea Institute of Construction Technology
5Professor, Dept. of Disaster Science, University of Seoul
Correspondence:  Myong-O Yoon, Tel: +82-2-6490-5376, Fax: +82-2-6490-5380, 
Email: u2u21976@naver.com
Received: 20 November 2019   • Revised: 2 December 2019   • Accepted: 2 December 2019
요약
본 연구는 화재 시 열출력 급상승 구간에 대한 정확한 열방출율을 예측하기 위한 새로운 함수를 개발하여 제안하는 것을 목적으로 하였다. 현재 화재공학에서 사용되고 있는 ‘αt2’ 곡선은 화재시스템 공학 관점에서 비효율적이며 실효성 저하를 초래하므로 열방출율의 예측오차를 최소화시킬 필요가 있다. ‘αt2’ 과 비교하여 보다 논리적인 배경과 형태적으로 유사성을 가진 로지스틱 함수 이론을 기반으로 화재 급성장 구간은 물론 화재 초기 단계까지 적용 가능한 새로운 예측 함수를 개발하였다. 개발된 함수는 더 넓은 화재성장 구간에서 정확도 높은 예측결과를 갖는 것으로 본 연구에서 증명되었다. 이 연구결과는 향후 화재성장패턴 연구의 개발과 함께 화재공학의 발전을 위해 적용될 것이다.
Abstract
In this study, a new function with higher accuracy for fire heat release rate prediction was developed. The ‘αt2’ curve, which is the major exponential function currently used for fire engineering calculations, must be improved to minimize the prediction gap that causes fire system engineering inefficiency and lower cost-effectiveness. The newly developed prediction function was designed to cover the initial fire stage that features rapid growth based on logistic function theory, which has a more logical background and graphical similarity compared to conventional exponential function methods for ‘αt2’. The new function developed in this study showed apparently higher prediction accuracy over wider range of fire growth durations. With the progress of fire growth pattern studies, the results presented herein will contribute towards more effective fire protection engineering.
Key Words: Heat release rate (HRR), Logistic function curve, Inversed logistic function curve, FDS simulation, Fire protection system detection sensor
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 0 Crossref
  •    
  • 79 View
  • 4 Download
Related articles in Fire Sci. Eng.


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
22, Teheran-ro 7-gil, Gangnam-gu, Seoul 06130, Republic of Korea
Tel: +82-2-555-2450    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2020 by Korean Institute of Fire Science and Engineering. All rights reserved.

Developed in M2community

Close layer
prev next