Fire Sci. Eng. > Volume 27(1); 2013 > Article
Journal of Korean Institute of Fire Science and Engineering 2013;27(1):52-59.
DOI: https://doi.org/10.7731/KIFSE.2013.27.1.052    Published online February 28, 2013.
소방펌프차의 고압방수를 위한 중계방수방식에 관한 실증적 연구
민세홍, 권용준, 박종덕
1가천대학교 공과대학 소방방재공학과
2가천대학교 환경.디자인대학원 소방방재공학과
3가천대학교 환경.디자인대학원 소방방재공학과
An Empirical Study on the Relay Pumping Method for the High Pressure of Fire Engine Pump
Min Se-Hong, Kwon Yong-Joon, Park Jong-Deok
1Dept. of Fire & Disaster Protection Engineering, Gachon Univ.
2Dept. of Fire & Disaster Protection Engineering, Graduate School Environment & Design, Gachon Univ.
3Dept. of Fire & Disaster Protection Engineering, Graduate School Environment & Design, Gachon Univ.
요약
본 연구에서는 초고층 건물 화재 등 고압방수가 필요한 상황에서 방수압력을 유지하기 위하여 소방펌프차의 중계방수방법과 활용방안을 정립하고자 시험을 실시하였다. 중계 방수압력의 변화에 대하여 시험결과 소방펌프차의 방수구를 개방하고 측정하였을 경우 방수구를 폐쇄한 상태에서 측정한 결과보다 약 20 %가 감소한 것으로 나타났다. 소방활동 현장에서 보다 더 효율적으로 활용하기 위하여 소방펌프차 2대의 압력을 각각 변화시키면서 시험한 결과에서도 비슷한 효율이 나타나는 것으로 확인되었다. 현재 고압 방수능력이 있는 소방펌프차가 소방서에 배치되어 있지 않고 소방펌프의 형식승인 및 검정기술기준에서도 고압 소방펌프에 대한 규정이 없기 때문에 현재 보유하고 있는 소방차를 활용하여 초고층 화재 등 고압방수의 필요성이 있는 화재현장에 효과적으로 대응하고자 본 연구 결과를 토대로 소방차량 운영 및 활용방안을 제안한다.
Abstract
In this study, tests were conducted to establish a fire engine of relay waterproof and utilization in order to maintain the pressure in a situation that require high-pressure water-resistant such as a high-rise building fire, etc. As a result of test on the change of a relay waterproof pressure, the measurement result with the hydrant intake of a fire engine opened has reduced approximately 20 % compared to the measurement result with the hydrant intake closed. Similar efficiency showed in the test result that change the pressure of 2 fire engines respectively to use them more efficiently at a fire fighting activity site. A fire engine operation and utilization is proposed based on this study result in order to cope effectively with a fire site requiring high-pressure stream in a high-rise building fire, etc. by using a fire engine held at present because there is no fire pump with high-pressure stream ability arranged at the fire station and there is no regulation on high-pressure fire-fighting pumps in a type approval and verification technology criterion for a fire engine.
Key Words: Fire engine, Multistage, Relay stream, Fire-fighting


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next