Fire Sci. Eng. Search

CLOSE


Fire Sci. Eng. > Volume 28(5); 2014 > Article
Fire Science and Engineering 2014;28(5):8-13.
DOI: https://doi.org/10.7731/KIFSE.2014.28.5.008    Published online October 31, 2014.
PCITS에 의해 소손된 1Φ 2 W MCCB의 탄화 패턴 및 작동 특성
이재혁, 최충석
1전주대학교 소방안전공학과
2전주대학교 소방안전공학과
Carbonization Patten and Operation Characteristics of a 1Φ 2 W MCCB Damaged by PCITS
Lee Jae-Hyuk, Choi Chung-Seog
1Dept. of Fire Safety Engineering, Jeonju University
2Dept. of Fire Safety Engineering, Jeonju University
요약
본 연구에서는 대전류공급장치시스템(PCITS)을 이용하여 열동전자식 배선용차단기(MCCB)에 과전류를 인가하였을 때 소손된 패턴을 해석하는 데 있다. MCCB의 트립바가 소손된 상태에서 PCITS로 과전류 150 A를 5 s 동안 흘렀을 때 우측에 위치한 온도 조절 장치의 표면이 심하게 탄화되었다. 동일한 조건에서 300 A의 과전류를 5 s 동안 흘렸을 때 온도 조절 장치의 전체가 열화(劣化)되어 납작하게 밀착되었다. 과전류 450 A를 5 s 동안 흘렸을 때 온도 조절 장치의 코일은 융융 및 단선이 발생하였다. 또한 접점, 외함 및 상부 덮개 등에서 탄화 흔적 및 변형이 확인되었다. 과전류600 A를 공급하고 3 s 정도가 경과되었을 때 MCCB의 내부에서 흰색 연기가 발생하였고, 불꽃이 외부로 방사되었다. 그리고 탁(딱)하는 소리와 동시에 과전류의 공급이 중단되었다. 동일한 MCCB를 일반 화염으로 소손시켰을 때 작동 손잡이, 단자, 소호 장치 및 온도 조절 장치 등의 표면에 탄화가 고르게 형성된 것을 알 수 있다. 또한 작동 기구부의 트립바는 녹아 흘러 내렸으며, 작동 금속핀은 트립 상태로 이동된 것이 확인된다.
Abstract
The purpose of this study is to analyze the damage pattern when overcurrent is applied to a thermal magnetic type molded case circuit breaker (MCCB) using a Primary Current Injection Test System (PCITS). When an overcurrent of 150 A was applied to the PCITS for 5 seconds with the trip bar of an MCCB being damaged, it was found that the surface of the temperature control device (bimetallic strip) positioned at the right was significantly carbonized. When an overcurrent of 300 A was applied to the PCITS for 5 s under the same conditions, the entire temperature control device was deteriorated, becoming flattened and in close contact with the MCCB. When an overcurrent of 450 A was applied to the PCITS for 5 s, the coil of the temperature control device was melted and disconnected. In addition, it was observed that the contacts, the enclosure and upper cover were deformed and there was a trace of carbonization on them. When approximately 3 s had elapsed after an overcurrent of 600 A was applied, white smoke occurred inside the MCCB and a flame was radiated out, after which the overcurrent supply stopped with "phutt" (whomp) sound. It was observed that when the same type of MCCB is damaged by a general flame, the surfaces of its handle, terminal, arc divider (extinguisher) and temperature control device were carbonized uniformly. In addition, it was found that the trip bar of the operating mechanism was melted down and the metal operation pin was moved while being tripped.
Key Words: Carbonization patten, Operation characteristics, MCCB, PCITS, Overcurrent, Trip bar
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 1 Crossref
  •    
  • 912 View
  • 6 Download
Related articles in Fire Sci. Eng.


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2025 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next