선박 내 CO2 소화설비에 의한 질식사고 방지 기법
하연철, 서정관, 황준호, 임기창, 류상훈
1부산대학교 선박해양플랜트기술연구원(로이드선급재단 우수연구센터)
2부산대학교 선박해양플랜트기술연구원(로이드선급재단 우수연구센터)
3부산대학교 선박해양플랜트기술연구원(로이드선급재단 우수연구센터)
4부산대학교 선박해양플랜트기술연구원(로이드선급재단 우수연구센터)
5(주)페스텍
Method for Preventing Asphyxiation Accidents by a CO2 Extinguishing System on a Ship
Ha Yeon-Chul, Seo Jung-Kwan, Hwang Jun-Ho, Im Kichang, Ryu Sang-Hoon
1The Korea Ship and Offshore Research Institute (The Lloyd's Register Foundation Research Centre of Excellence), Pusan National University
2The Korea Ship and Offshore Research Institute (The Lloyd's Register Foundation Research Centre of Excellence), Pusan National University
3The Korea Ship and Offshore Research Institute (The Lloyd's Register Foundation Research Centre of Excellence), Pusan National University
4The Korea Ship and Offshore Research Institute (The Lloyd's Register Foundation Research Centre of Excellence), Pusan National University
5FESTEC INTERNATIONAL Co., Ltd.
요약
육상 및 해상에서 일어나는 화재를 진압하기 위한 가스계 소화설비 중 이산화탄소 소화설비는 우수한 성능 및 높은 경제성으로 인하여 널리 사용되고 있지만, 고농도 이산화탄소로 인한 질식사고가 빈번히 발생하여 안전문제가 항상 지적되어 왔다. 본 연구에서는 수치해석을 통하여 선박 내 압축기실의 이산화탄소 소화설비 화재 진압 특성을 예측하고, 이산화탄소 소화설비로 인한 질식사고를 방지하기 위한 2중 안전 제어기법을 제시하여, 이산화탄소 소화설비의 안전을 도모하였다. 수치해석 결과로는 4가지 시나리오를 선정하여, 화재발생 후 이산화탄소 소화설비 작동으로 인한 열발생률 변화, 온도변화, 이산화탄소 농도변화, 산소 농도변화 및 화재진압 특성을 고찰하였으며, 방호구역 내 환기팬 용량이 충분하지 않은 경우의 위험성 및 적절한 환기시스템의 필요성을 제시하였다.
Abstract
Carbon dioxide extinguishing systems are broadly used for onshore and offshore fire accidents because of excellent performance and low cost. However, there is risk with carbon dioxide systems, which have caused many injuries and deaths by suffocation associated with industrial and marine fire protection applications. In this study, a numerical analysis was performed to predict the fire suppression characteristics of a carbon dioxide system in the compressor room of ships. A double protection safety system is suggested to prevent suffocation accidents from carbon dioxide extinguishing systems. Four scenarios were selected to study the variation of the heat release rate, maximum temperature, a $CO_2$ and $O_2$ mole fraction, and fire suppression characteristics with the carbon dioxide system. The importance of proper design is suggested for a ventilation system in the compressor room of ships.
Key Words: $CO_2$ extinguishing system, FDS, Safety system, Suffocation accident, Compressor room, Sensor system


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next