Fire Science and Engineering 2016;30(3):55-61.
DOI: https://doi.org/10.7731/KIFSE.2016.30.3.055    Published online June 30, 2016.
PE 이종강관의 소방용 배관 적용성에 관한 실험적 연구
박정화, 오천영, 곽지현, 손봉세
1가천대학교 일반대학원 설비.소방공학과
2가천대학교 일반대학원 설비.소방공학과
3한국화재보험협회 부설 방재시험연구원
4가천대학교 설비.소방공학과
An Experimental Study on Piping Feasibility of PE Compound Pipe for Fire Protection Service
Park Jeong-Hwa, Oh Cheon-Young, Kwark Ji-Heon, Son Bong-Sei
1Dept. of Building Equipment System & Fire Engineering Graduate School, Gachon Univ.
2Dept. of Building Equipment System & Fire Engineering Graduate School, Gachon Univ.
3Fire Insurers Laboratories of Korea
4Dept. of Building Equipment System & Fire Engineering, Gachon Univ.
요약
본 연구는 현재 사용하고 있는 소방용 배관의 부식으로 인하여 발생하는 수계소화설비의 문제를 해결하기 위하여 개발한 Polyethylene (PE) 이종강관을 수계소화설비배관으로 적용할 수 있는지를 파악하기 위한 실제 화재시험을 수행하였다. 개발된 이종배관에 대한 관련시험기준이 없어 국내외 기술자료 및 시험기준을 비교분석하여 적합한 화재시험기준을 선정하여 PE 이종강관의 성능을 분석하였다. 따라서 본 배관의 성능시험에 채택한 화재시험기준은 합성수지배관과 금속배관의 두 가지의 화재시험기준을 적용하였고 총 6차례의 화재실험을 실시하여 배관성능을 평가하였다. 소방용합성수지배관의 시험기준을 적용한 1, 2차의 화재시험결과 이음쇠와 배관에서 파손이나 변형이 없었으며 5분간 내압시험을 실시한 결과에서도 누수가 없었다. 금속배관시험기준을 적용한 화재실험은 총 4회를 실시하였으며 1, 2차 실험은 습식설비를 모사한 것으로 화재시험결과는 PE 이종강관에서 누설이나 파열이 발생하지 않았으며 또한 PE 재질의 이탈 등 손상이 발생되지 않음을 확인하였다. 단, 건식설비를 모사한 3, 4차의 화재시험결과 소화수가 방출되기 이전에 PE 이종강관에서 파열, 변형 등의 손상이 발생하였다. 따라서 실험결과 습식설비를 모사한 화재시험의 경우 PE 이종강관의 융착성, 변형, 파손 등 배관의 성능에 이상이 없음을 확인하였다.
Abstract
In this study, to determine whether it is possible to apply Polyethylene (PE) compound pipe, which was developed to solve the problem caused by the corrosion of the fire protection piping currently in usein water based fire extinguishing systems, we performed an actual mockup fire test. Since no test standard was available related to the developed compound pipe, we compared and analyzed domestic and international technical materials and test standards and selected suitable fire test standards to evaluate the performance of the PE compound pipe. we applied two fire test standards to the PE compound pipe, viz. those for CPVC and metallic pipes, and conducted a total of 6 experiments to evaluate its performance. According to the results of the first and second fire tests based on the test standard for the CPVC pipe, neither the fitting nor the piping was damaged or deformed and no leakage was observed in the pressure test, which was performed for 5 minutes. For the fire test based on the metallic pipe test standard, a total of 4 experiments were conducted. The first two experiments were conducted to simulate the wet piping system. In the results of this fire test, neither leakage nor rupture was observed from the PE compound pipe and no damage was caused, such as the secession of the PE material. However, in the next two experiments, which simulated the dry system, the PE compound pipe suffered damage and rupture, including deformation before the fire fighting water was discharged. Therefore, we found that the piping performance of the PE compound pipe did not undergo any deterioration, including fusion, deformation, or damage, in the wet piping system simulated fire test.
Key Words: Polyethylene (PE) compound pipe, Chlorinated polyvinyl chloride (CPVC) pipe test, Metallic sprinkler pipe test, Feasibility, Mockup fire test, Corrosion


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next