Fire Science and Engineering 2016;30(5):60-66.
DOI: https://doi.org/10.7731/KIFSE.2016.30.5.060    Published online October 31, 2016.
건축재료별 목재구조와 연소특성에 관한연구
김종북, 박영주, 이시영
1강원대학교 방재전문대학원
2강원대학교 공학대학 소방방재학부
3강원대학교 방재전문대학원
Star Building Materials Study on Wood Structure and Combustion Characteristics
Kim Jong-Buk, Park Young-Ju, Lee Si-Young
1The Professional Graduate School of Disaster Prevention Technology, Kangwon National Univ.
2Department of Fire & Emergency Management, Engineering College, Kangwon National Univ.
3The Professional Graduate School of Disaster Prevention Technology, Kangwon National Univ.
요약
본 연구는 건축 재료(마감재)로 쓰이고 있는 목재 나무류 미송, 나왕, 삼나무, 소나무 등4종의 구조와 연소특성을 연구하였다. 착화특성을 보면 착화시간(TTI)범위가 21 s~32 s으로나타났으며 특히 소나무는 TTI가 21 s로 다른 재료들보다 비교적 빠른 601 s에 착화되어 631 s에 소멸되었다. 최대열방출율과 평균열방출율은 소나무 > 나왕 > 삼나무 > 미송 순으로 나타내었다. 총열방출량은 나왕 > 미송 > 소나무 > 삼나무 순이었다. 총연기방출량은 소나무가 $424.80m^2/m^2$, 나왕 $185.93m^2/m^2$이었다. 탄소배출량은 미송이 1,460 s에서 0.185 kg/kg CO 최대값을 보이고 $CO_2$ 값은 750 s에서 15,986 kg/kg으로 최대값을 보이다 3,090 s에서 정지되었다. 향후, 건축 재료로서 화재의 안전성을 평가하기 위한 기초 자료로 활용하는 방안을 제시하였다.
Abstract
This study investigated the structure and combustion characteristics of four species, Timber Douglas-fir being used construction materials (finishes), Lauan, Cryptomeria japonica, Pinus densiflora trees in the area. In lookong into the ignition characteristics was a time range of ignition (TTI) appeared in the 21 s~32 s, especially Pinus densiflora TTI is ignited in a relatively rapid 601 s to 21 s than the other materials were destroyed in the 631 s. The maximum heat release rate and average heat release rate is Pinus densiflora > Lauan > Cryptomeria japonica > Douglas-fir showed a net. Barrel emissions are Lauan > Douglas-fir > Pinus densiflora > Cryptomeria japonica was in order. The total emissions was postponed Pinus densiflora $424.80m^2/m^2$, Lauan $185.93m^2/m^2$. Douglas-fir carbon emissions of 1460, showing 0.185 kg/kg CO maximum value from s $CO_2$ values show the maximum value to 15,986 kg/kg in 750 s stopped in the 3,090 s. Next, the study suggested methods to utilize as the basic data for evaluating the safety of the fire as a building material.
Key Words: Structure, Combustion characteristics, Cryptomeria japonica, Pinus densiflora, Building material


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next