Fire Science and Engineering 2018;32(6):28-33.
DOI: https://doi.org/10.7731/KIFSE.2018.32.6.028    Published online December 31, 2018.
건축물 구획공간에 따른 화재성상 및 열방출율 측정에 관한 실험적 연구 - 실물규모 침대 매트리스 화재시험 중심으로 -
서보열, 장우빈, 박계원, 홍원화
1방재시험연구원.경북대학교 건축학부 대학원
2방재시험연구원
3방재시험연구원
4경북대학교 건축학부
Experimental Study on the Measurement of Fire Behavior and Heat Release Rate in Building Compartment Space - Focus on Full Scale Fire Test of the Bed Mattress -
Seo Bo-Youl, Jang Woo-Bin, Park Kye-Won, Hong Won-Hwa
1Fire Insurers Laboratories of Korea.Dept. School of Architecture, Kyungpook National Univ.
2Fire Insurers Laboratories of Korea
3Fire Insurers Laboratories of Korea
4School of Architecture, Kyungpook National Univ.
요약
건축물 구획공간에 따른 화재성상 및 열방출율을 측정하기 위하여 실물규모 침대 매트리스의 표준화재시험방법(KS F ISO 12949 : 2011)으로 화재시험을 수행하였다. 개방형공간과 구획공간 모두 버너착화 후 초기 약 3분까지는 유사한 화재성장의 경향을 보이는 것으로 확인되었다. 3분후 구획공간에서의 열방출율이 개방형 공간보다 증가되어 높은 것으로 확인되었다. 침대 매트리스(SS)의 경우, 개방형 공간에서의 최대열방출율은 735 kW이며, 구획공간에서의 최대열방출율은 992 kW 로 측정되었다. 침대 매트리스(Q)의 경우 3분후 구획공간에서의 열방출율이 개방형 공간보다 급격하게 증가되는 것으로 확인되었다. 개방형 공간에서의 최대열방출율은 1,087 kW, 이 때의 측정시간은 346s 이며, 구획공간에서의 최대열방출율은 2,127 kW, 이때의 측정시간은 287 s 측정되어 구획공간에 따른 최대열방출율 및 측정시간의 차이가 확인되었다.
Abstract
To measure the full scale fire test and heat release rate of bed mattresses according to the building compartment space, a fire test was performed using the Standard test method to determine the heat release rate of mattresses and mattress sets (KS F ISO 12949: 2011). Both test locations showed similar fire growth until approximately 3 minutes after burner ignition. After 3 minutes, the heat release rate in the test room was higher than the open calorimeter. For bed mattresses (SS), the maximum heat release rate in the open calorimeter was 735 kW and the maximum heat release rate in the test room was 992 kW. For bed mattresses (Q), the heat release rate in the test room increased more rapidly than the open calorimeter. The maximum heat release rate in the open calorimeter was 1,087 kW (346 s) and the maximum heat release rate in the test room was 2,127 kW (287 s). The difference between the maximum heat release rate and the measurement time according to the test location was confirmed.
Key Words: Building compartment space, mock-up test, Heat release rate, Bed mattress, Fire behavior


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next