Fire Sci. Eng. > Volume 33(3); 2019 > Article
Fire Science and Engineering 2019;33(3):1-8.
DOI: https://doi.org/10.7731/KIFSE.2019.33.3.001    Published online June 30, 2019.
콘칼로리미터 연소가스 FT-IR 분석을 위한 국제표준 초안의 비교시험 결과분석
최정민1, 박계원2, 정재군3
1한국화재보험협회 부설 방재시험연구원 화재환경시스템팀 선임연구원
2한국화재보험협회 부설 방재시험연구원 화재환경시스템팀 책임연구원
3한국화재보험협회 부설 방재시험연구원 화재환경시스템팀 수석연구원
Results of a Round-Robin Test for the Draft International Standard on FT-IR Gas Analysis of Fire Effluents from a Cone Calorimeter
Jung-Min Choi1, Kye-Won Park2, Jae-Gun Jeong3
1Senior Researcher, Fire Safety & Building Environment Research Team, Fire Insurers Laboratories of Korea
2Senior Researcher, Fire Safety & Building Environment Research Team, Fire Insurers Laboratories of Korea
3Principal Researcher, Fire Safety & Building Environment Research Team, Fire Insurers Laboratories of Korea
Correspondence:  Jung-Min Choi, Tel: +82-31-887-6769, Fax: +82-31-887-6680, 
Email: jmchoi@kfpa.or.kr
Received: 5 March 2019   • Revised: 15 April 2019   • Accepted: 18 April 2019
요약
ISO TC 92에서는 콘칼로리미터의 연소가스를 FT-IR 방식의 가스분석기로 분석하기 위한 표준을 개발하고 있다. 2018년에는 표준 초안(WD 21397)의 절차에 따라 6개 기관이 참여하여 표준 초안의 반복성 및 재현성을 평가하였다. 시험대상 시료는 polymethyl methacrylate (PMMA), 경질 폴리우레탄 보드 및 PVC 장판이었고 콘칼로리미터 시험결과 중 착화시간(s), 최대 열방출률(kW·m-2), 총 방출열량(MJ·m-2) 및 유효연소열(MJ·m-2·kg-1)을, 그리고 FT-IR 가스분석결과 중 독성가스의 최대 농도(μL·L-1), 가스 발생량(g) 및 가스 수율(g·g-1)을 ISO 5725-2에 따라 통계 분석하여 정밀도를 평가하였다. 이상치(outlier)는 발견되지 않았으며 콘칼로리미터 시험의 반복성(sr/m)은 1.5%, 재현성(sR/m)은 9.8%로 나타났고 FT-IR 가스분석의 반복성은 12.9%, 재현성은 27.9%로 나타났다.
Abstract
The international standard for FT-IR gas analysis of fire effluents in ISO 5660-1 cone calorimeter has been being developed in ISO TC 92. A comparison of the round-robin test of WD 21397 was conducted with six participating laboratories in 2018. The test specimens were PMMA, rigid PU foam board, and PVC flooring. The measurement quantities were the time-to-ignition, peak heat release rate, total heat release, and effective heat of combustion for a cone calorimeter test and peak gas concentration, gas generation, and gas yield for FT-IR gas analysis. No outliers were identified. For the cone calorimeter quantities, the repeatability and reproducibility were 1.5% and 9.8%, respectively. For FT-IR gas analysis, the repeatability and reproducibility was 12.9% and 27.9%, respectively.
Key Words: Round-robin, Repeatability, Reproducibility, FT-IR, Cone calorimeter
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 0 Crossref
  •    
  • 1,412 View
  • 35 Download
Related articles in Fire Sci. Eng.


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next