1. 서 론
2. 문헌검토
2.1 연구사례 수집 및 분류
Table 1
2.2 연구사례의 키워드 분석
Table 2
| No | Keywords | Cases [Ref.] |
|---|---|---|
| 1 | Sodium, Fire, Extinguish Agent, Patent, Analysis, Component | 6 [4] |
| 2 | Sodium, Sodium Fire, Fire Extinguishing Material, Sodium Storage Facility, Firefighting, Metal Fire | 6 [7] |
| 3 | Sodium, Metal Fire, Firefighting Materials, Fire Extinguishing System | 4 [8] |
| 4 | Sodium, Storage, Handling, Sodium Fire, Extinguishant, Cover Gas, Protective Equipment | 7 [9] |
| 5* | LMFBR Type Reactors, Sodium, Fire, Sodium Leak, Sodium Pool Combustion, Combustion Heat, Diffusion Flame, Heat Transfer, Mass Transfer, Reactor Safety, Computer Calculations, Computer Codes | 12 [11] |
| 6 | Chemistry, Fire, Liquid Metal | 3 [14] |
| 7* | LMFR, Sodium Fire, Sodium Oxides, Instantaneous Chemical Equilibrium, Diffusion Flame, Aerosol, Aerosol Transport, Release Fraction | 8 [15] |
| 8 | Fire Safety, Sodium Pool Fire, Numerical Simulation | 3 [16] |
| 9* | SFR Safety, Sodium Fire Safety, Sodium Pool Fire, Pool Spreading, Instantaneous and Continuous Spills, Integral Spreading Model | 6 [18] |
| 10* | Sodium Aerosols, Aerosol Modeling, HAARM Code, Aerosol Size Growth, Method of Moments | 5 [19] |
| 11 | SFR Safety, Sodium Pool Fire, Liquid Spill Spreading, Viscous-Gravity Current, Shallow Layer Model | 5 [20] |
| 12 | Sodium, Fire, Powder, Physicochemical, Extinction | 5 [34] |
| 13 | SFR, Argon, Metal Fire, Clean Gas Agent, Sodium | 5 [35] |
| 14 | Inert Gas, Extinguishing Agent, Metal Fire, Oxygen Concentration, Metallic Combustibles | 5 [36] |
| 15 | LMFR, Sodium, Columnar Flow, Columnar Fire, Pool Fire, Spray Fire, Temperature Field | 7 [38] |
| 16 | Sodium Fire, Extinguishing, Expandable Graphite, Stearate Sodium, Core-Shell Structure | 5 [39] |
| 17 | Sodium Spray Fire, Particle Generation, SFR, Numerical Model Development | 4 [40] |
| 18 | Fire Extinguishing, Expandable Graphite, Sodium Fire, Fire Control Mechanism | 4 [41] |
| 19 | Fire Suppression, Expandable Graphite Powder, Sodium Fire, Fire Control Mechanism | 4 [42] |
| 20 | KHCO3, Suppressants, Hydrophobic Properties, Decomposition, Crystal Phase | 5 [43] |
| 21 | Engineering Test, Fire Extinguishers, Test Procedure, Test Methods and Techniques | 4 [44] |
| 22 | Hydrogen Safety, Combustible Dusts, Fire Suppression, Suppression Agents, Hydrides, Hydride Fires | 6 [48] |
| 23* | LN2, Metal Combustion, Pool Fire, Suppression Agent | 4 [49] |
| 24 | Sodium Fires, Severe Accident Modeling, Historical Archives, Knowledge Preservation, ASTEC-Na | 5 [56] |
| Total | 133 | |
2.3 주요 연구사례의 실험 세부사항 검토
Table 3
| No | Experiment Details | [Ref.] | No | Experiment Details | [Ref.] | ||
|---|---|---|---|---|---|---|---|
| Summary and Result | Related Photos | Summary and Result | Related Photos | ||||
| 1 |
* Sodium Weight 10 g Hotplate Up to 500 °C * Powder (20 g) 13 Cases Na2CO3 Etc. |
|
[34] | 7 |
* Sodium Weight 5.5 g Temperature Controller * Powder 4 Cases EG, KNO3 (g) |
|
[43] |
| 2 |
* Sodium Weight 10 g Reaction of Water * Gas Agent 6 Cases Ar gas (%) |
|
[35] | 8 |
* Sodium Weight 40 g Hot Plate * Gas Agent 4 Cases Liquid N2 (600~700 g) |
|
[47] |
| 3 |
* Sodium Weight 10 g Reaction of Water * Gas Agent 4 Cases Ar, N2 (%) |
|
[36] | 9* |
* Sodium Weight (0.5~10 kg) Oxy-Acetylene Flame (Direct) * Powder 8 Agent (Alumite Etc.) |
|
[17] |
| 4 |
* Sodium Weight 5 g Hotplate * Powder 3 Cases EG, SS (g) |
|
[40] | 10* |
* Sodium Weight 25 g Oxy-Acetylene Flame (Direct) * Powder 7 Cases ABC Etc. |
|
[37] |
| 5 |
* Sodium Weight 5 g Temperature Controller * Powder 3 Cases EG (g) |
|
[41] | 11* |
* Sodium Fire Case Safety * Agent 7 Cases Powder, Gas Etc. |
|
[50] |
| 6 |
* Sodium Weight 5 g Temperature Controller * Powder 3 Cases EG, ZB (g) |
|
[42] | 12* |
* Sodium Weight (0.3~10.5 kg) * Burn Pan 6 Cases Unique Feature |
|
[53] |
Table 4
| No | Safety Recommendation | [Ref.] | No | Safety Recommendation | [Ref.] | ||
|---|---|---|---|---|---|---|---|
| User & Ambient and Measures | Related Photos | User & Ambient and Measures | Related Photos | ||||
| 1 |
* Sodium Handling Procedures Gas Mask Heat-Radiating Suit Protective Goggles |
|
[14] | 4* |
* Sodium Experiment Protective Clothing Chrome Leader Aluminised Asbestos |
|
[50] |
| 2* |
* Sodium Pool Fire Experiment Provide the Person is Fully Covered Up with a Safety Suit |
|
[17] | 5* |
* Sodium Experiment Protective Clothing Safety Shield and Working |
|
[53] |
| 3* |
* Removal of Leaking Sodium Collection Barrel Vacuum Head Driving-Gas Cylinder |
|
[28] | 6* |
* Sodium Experiment Safety Workbench Glovebox Cylindrical & Moving Compartment Section |
|
[59] |
2.4 국내 규정사항 수집 및 분석
Table 5
2.5 국외 규정사항 수집 및 분석
Table 6
3. 고려사항 선별 및 논의
3.1 일반사항
Table 7
3.2 논의 및 한계
4. 결 론
1) 연구사례의 분석을 통해 핵심키워드 3개(fire, sodium, pool)를 발췌하여 sodium pool fire test로서 Na금속 화재 및 소화시험의 수행항목으로 선별하였고 보조키워드 8개(aerosol, metal, safety, agent, extingushing, model, suppression, SFR)를 발췌하였다. 이를 바탕으로 주요연구사례 및 내용을 선별하여 화원시료의 중량, 점화장치 및 방법, 적용소화약제 등 실험 세부적으로 요구되는 사항을 확인하였다. 또한 방열복, 보안경, 방독면과 같은 개인안전물품, 화원시료 전후처리를 위한 작업대 및 안전장치 제작 등 작업자의 안전사항 및 권고조치에 대한 필요성도 확인하였다. 이는 소화약제, 소화기 등 성능수준 평가만큼 시험자가 화원시료를 진압하는 과정에서 발생하는 에어로졸, 분진, 부유물 등과 같은 물질로부터 인명보호와 화재⋅폭발 등으로부터 방호조치 등이 요구됨과 상응한다고 판단된다.
2) 규정사항의 분석을 통해 현재 국내 규정의 특징을 확인하였고 국외에서 규정하고 있는 Na화재 및 소화시험방법 등에 대해 검토하였다. 수행항목으로 설정한 sodium pool fire test는 규정사항 분석을 통해 ISO 7165와 UL711에 금속화재 항목에도 유사한 시험이 존재하고, 실질적인 수요처가 될 수 있는 SFR의 형태 및 모양 등을 고려할 때 적합한 시험방법이라고 판단된다.
3) 고려사항 선별을 통해 설계절차 작성 예시를 제시하였고, 실물실험 등 연구수행을 통해 단계적으로 수정⋅보완하고자 한다. 아울러 Na화재 및 소화시험의 절차, 방법에 대한 구체화 방안 마련과 Na화재 및 소화시험을 위한 장비⋅시설 등 구축방안도 향후 연구를 통해 논의하고자 한다. 또한 연구의 한계인 키워드 세부분석 내용 설정과, 고려사항의 다각적 분석 등은 추가적으로 실시하여 연구수행에 있어 방향성과 내용을 지속 보완하고자 한다.