Journal of Korean Institute of Fire Science and Engineering 1988;2(3):3-9.
Published online November 30, 1988.
방화구획과 수막설비 관한 연구
오창희, 손장열, 김화중, 김상욱, 최진
1한양대학교 건축공학과2한양대학교 건축공학과3경북대학교 건축공학과4이광엔지니어링5한국방재연구
Experimental study of water membrane sprinkler in fire prevention block
Oh Chang-Hui, Son Jang-Yeol, Kim Hwa-Jung, Kim Sang-Uk, Choi Jin
Abstract
This paper is study about establishment with water membrane sprinkler in fire prevention block of special Building. The testing program was directed toward investigating the temperature of fire and adjacent room. The results of fire test indicated that under the test conditions in this study, adjacent room temperature is very low in compare with fire room temperature at operating of water membrane sprinkler. Therefore, if exclusion of smoking can be soluted, substitution of water membrance sprinkler in fire resistance wall of fire prevention block is possible.