Journal of Korean Institute of Fire Science and Engineering 2001;15(2):46-52.
Published online June 30, 2001.
스프링클러 반응시간 예측에 대한 화재모델의 비교
김종훈김운형이수경
1경민대학 소방안전관리과2경민대학 소방안전관리과3서울산업대학교 안전공학과
A Comparison of the Prediction of Sprinkler Response Time Applying Fire Models
Abstract
To evaluate the usability of compartment fire models for predicting sprinkler response time, fire experiment was conducted and measured sprinkler response time. The experimental data was compared with zone model "FASTLite"and field model "FDS"and field Model "SMARTFIRE" A Compartment fire conducted in a 2.4 m by 3.6 m by 2.4 m ISO 9705 room and measured H.R.R was approximately 100.3 kW. In test, Sprinkler activation temperature used is $72^{circ}c$ and responded at 198s. The output of FASTLite, SMARTFIRE and, FDS for this fire scenario were 209s, 183s, and 192s, respectively. As a results, prediction using FDS model approached to that of test very closely and other models showed good approximated results also.
Key Words: Sprinkler response time, FASTLite, SMARTFIRE, FDS models